◆用途和适用范围
Pupose and scope
H20-60电涌保护器(以下简称''保护器''}适用于交流50/60Hz、400V 及以下的TN-S、TN-C、TN-C-S、TT、IT等供电系统,对电网因雷击或浪涌过电压进行保护。

H20-60 surge prote ction device {hereinafter refened to as the

'prote ctor'} for AC 50/60Hz,400V and below the TN-S, TN· C. TN-C-S, TT, IT power supply system, the power grid caused by lightning or

surge voltage protection,


失效脱离装置

From the device failure

保护器的模块上设有失效脱离装置,当保护器因过热,击穿失效时,失效脱离装置能自动的将其从电网上脱
离,同时给出指示信号。保护器正常时标牌显示绿色、失效脱离后标牌显示红色。
Module protector with failure from the device, when the protective device due to overheating. Break-
down failure, failure from the device can automatically from the power offFrom the, also g lve an indication
signal. Protector normal signs shown in green, red label display failure detachment.


保护器的外形及安装尺寸

And installation dimensions protector shape


安装位置与应用  The installation posltion and Application
安装在LPZ1或LPZ2区与LPZ3区交界处,保护级别Ⅱ级。
保护器采用标准的35mm轨道安装
保护器采用2 5-35mm2的铜质导线联接,其接线方法有两种
(1)从电源开关联线到保护器,再从保护器联线到负载端。这种方法适用于负载电流100A以下的配电箱。使
用导线截面应该按负电流选用(见图1)
(2)从电源开关联线到保护器,还从电源开关联线到负载端。这种方法适用子负载电流100A以上的配电箱。
联接到保护器的导线截面不受负载电流的影响,但长度不得过500mm(见图2)。
接地线应采用4mm2以上的双色导线,长度不得过500mmo。
为了防止电涌保护器失效后影响电网正常运行,联于L线的保护器应该串接一个32A的熔断器。
Installed In the LPZ1 or LPZ2 area and LPZ3 area allhe Junction, protection class [i,
Protective device using standard 35mm track installation
Protector adopts a copperwire connected to the 2,5-35-mm2, there are two kinds of wiring meth od
(1) from the power supply switch wiring to the protector, and the protector line to the load side. This
method is suitable for load distribution box electric current below 100A. The use of wire sec» on should be
selected according to the load curr-ent(see Fig ure 1)
(2) from the power supply switch wiring to the protector, also from the line to the load side power swi-
tch. This applies to the load current is more than 1 DOA power distribution box. Co-
nnected to the protective conductor cross section is not affe cted by the load of el-
ectrlclty, but the length shall nol exceed 500mm(see Figure 2).
The grounding wire should be used more than 4mm2 of dual color wire len-

gth. shall not exceed 500mm.
In order to prevenllhe surge protection device rallure affects the normal op-
eration of power grld, pl otection on the L line should string fuse are connected with
a 32A 1.

调整、使用、维护 Adjustment,use,maintenance
SPD按要求安装后不需要调整
只要SPD安装得当即可自动对电网进行保护
运行中要定期检查模块标牌是否发红,及时更换失效元件
According to the requirements on the SPD installation does not need to be adjusted

As long as SPD is properly Installed on the power grid can be automatlc protection;
Operation should regularly check module label is red, the timely replacement of failure

element.